Divi Essential Documentation

⌘K
  1. Home
  2. Docs
  3. Divi Essential Documentat...
  4. xc2003 controller manual
  5. xc2003 controller manual

Xc2003 Controller Manual

The manual describes setting a “soft limit zone” via parameter P30 (negative limit) and P31 (positive limit). When reached, the controller stops without triggering a hardware limit alarm.

The most referenced section of the xc2003 controller manual is the wiring diagram. Incorrect wiring accounts for 80% of initial setup failures. Below is a paraphrased guide based on the official manual.

The XC2003 often serves as a dedicated motion controller for stepper or servo axes. The manual treats this not as an afterthought, but as a core competency. xc2003 controller manual

Look for the "Pulse Output Parameter Table" . This section explains:

This is where 90% of user errors occur. The XC2003 manual specifies that inputs are active low. The manual describes setting a “soft limit zone”

Critical Note from the Manual: Do not apply external voltage to these pins. Use the internal 5V via a pull-up resistor or use mechanical NC (Normally Closed) switches.


Manual solution: Re-install CH340 driver after disabling Windows driver signature enforcement. Also, ensure the controller is in “USB Mode” (DIP switch 1 = ON, switch 2 = OFF). Critical Note from the Manual: Do not apply


Relay output (RL1) controls spindle on/off. The analog output (0-10V) controls RPM. Manual diagram shows:


For advanced users, the XC2003 can act as a Modbus slave via RS485 (pins on J7). Register addresses are listed in manual page 48: Holding register 0x0001 = current X position (32-bit float).


The XC2003 has dedicated input pins: X-LIMIT, Y-LIMIT, Z-LIMIT. The manual insists on normally closed (NC) switches for failsafe operation.